UMAC Medium to High Pressure Excess Flow Valves
For Propane (LPG) Services
5 psig to 720 psig—Inlet Pressure

All valves comply with DOT Part 192.381 and MSS SP-115: Excess Flow Valves for Fuel Gas Service

1.55 SPECIFIC GRAVITY (SG) PROPANE GAS
For pressure, flow, trip, and reset characterisitics for other applications,
please call your UMAC representative or contact GasBreaker headquarters.
         Flow Prior to Closure (Trip), SCFH 1.55 SG Gas  
    (Nominal Minimum) Bleed-By Flow
Inlet       After Closure (Trip)
Pressure SERIES 300 SERIES 700 SERIES 1800 SCFH 1.55 SG Gas
psig (BLACK LABEL) (ORANGE LABEL) (GREEN LABEL) (Nom. Max.)
5 249 373 1120 11
10 280 435 1244 12
15 305 473 1400 14
20 336 516 1555 16
30 386 597 1742 17
40 423 659 1928 20
50 460 746 2115 22
60 498 809 2364 23
70 535 877 2550 24
80 566 921 2675 26
90 591 958 2799 29
100 622 995 2923 31
150 740 1107 3278 47
200 753 1219 3816 53
250 840 1331 4292 72
300 927 1443 4749 81
1)  Flow Prior to Trip values in chart for 5 to 100 psig represent Nominal Minimum values ;
to obtain Nominal Maximum flow prior to trip values, multiply Nominal Minimum value by
the following factors :
1.34 for the Series 300 
1.35 for the Series 700
1.29 for the Series 1800
2)   Flow values from 150 - 720 psig represent Nominal Minimum flow prior to trip values.
3)   Bleed-By flow after trip values represent Nominal Maximum values.
4)   Minimum service size for Series 1800 valve must be 3/4" IPS or 1" CTS.
NOTE : Calculate service line capacities from given flow and pressure drop data below to ensure that
adequate flow capacity is available to operate valve.  For additional assistance in sizing and
 technical information on GasBreaker valves, please contact GasBreaker.

Please Note:
The technical data contained herein are guides to the use of UMAC Valves. The advice contained herein is based upon tests and information believed to be reliable, but users should not rely upon it absolutely for specific applications. It is given and accepted at user's risk and confirmation of its validity and suitability in particular cases should be obtained independently. GasBreaker, Incorporated makes no guarantee of results and assumes no obligation or liability in connection with its advice. This publication is not to be taken as a license to operate under or infringe any patents.

Home  |  EFV Benefits  |  Products  |  Sizing Guidelines  |  Customer Login  |  About Us
Valve Sizing Request  |  Contact Us  |  Residential Applications  |  Terms of Use

GasBreaker Incorporated
17 Lee Blvd. Ste. D  •  Malvern, PA 19355-1234  •  1-800-524-0566  •  610-407-7200  •  Fax: 610-407-7211  •   Email: info@gasbreakerinc.com

© 2009-2011 GasBreaker, Inc.